This is the ideal test tool for maintenance, troubleshooting and performance testing of individual stationary batteries and battery banks used in critical battery back-up applications. The intuitive user interface, compact design and rugged construction ensure optimum performance, test results and reliability. Covers a broad range of battery test functions ranging from DC voltage and resistance tests to full condition testing using automated string function testing and the test probe integrated infra-red temperature measurement system. The Fluke 500 Series are designed for measurements on stationary batteries of all types.

Key features

Fluke BT510 key features:

  • Battery Voltage – During the internal resistance test, Fluke Battery Analysers also measure the voltage of the battery under test
  • Discharge Volts – The Discharge mode collects the voltage of each battery multiple times at a user defined interval during a discharge or load test. Users can calculate the time a battery takes to drop to the cut-off voltage and use this time to determine the capacity loss of the battery
  • Ripple Voltage Test – Measures unwanted residual ac component of the rectified voltage in dc charging and inverter circuits. Allows users to test ac components in dc charging circuits and find one of the root causes of battery deterioration
  • Meter and Sequence Modes – The Meter mode is used for a quick test or troubleshooting. In this mode you can save and read the readings in a measurement or time sequence. The Sequence mode is for maintenance tasks with multiple power systems and battery strings. Before a task starts, users can configure a profile for the task for data management and report generation
  • Threshold and Warning – Users can configure a maximum of 10 sets of thresholds and receive a Pass/ Warning/ Fail indication after each measurement
  • Intercell Strap Resistance Test and Data Management – Measures the resistance of the intercell connection between batteries in a string. Once the measurements are completed Fluke Battery Management Software version 1.0.69 can now report the strap resistance for a battery string or historical data over time.
  • AutoHold – When AutoHold is turned on, a reading is captured when it remains stable for 1 second. The reading is then released when a new measurement starts
  • AutoSave – When AutoSave is turned on, measured values are saved to internal memory automatically after an AutoHold reading is captured
  • Fluke Battery Management Software – Easily import data from the Product to a PC. The measurement data and battery profile information is stored and archived with the Management Software and can be used for comparison and trend analysis. All measurement data, battery profile and analysis information can be used to easily generate reports
  • Comprehensive logging – All measured values are automatically captured during testing and can be reviewed on the instrument before downloading for on the-go analysis
  • Optimised user interface – Quick, guided setup ensures you’re capturing the right data every time
  • Battery life – 7.4 V 3000 mAh lithium-ion battery for more than eight hours continuous operation.
  • USB port – For fast data download to supplied data analysis and report management application software.
  • Highest safety rating in the industry – CAT III 600 V, 1000 V dc max. rated for safe measurements all around the battery power supply equipment.

Fluke BT520 Key features: (Designed for measuring batteries in cabinets and hard to reach places)

  • All of the above plus
  • BTL20 Interactive Test Probe set, with long and short probe extenders and built-in LCD display and speaker for visual and audio feedback
  • Large soft carry case

Fluke BT521 Key features: (Designed for users who need to incorporate temperature measuring)

  • All of the above* plus
  • BTL21 Intelligent Test Probes with long and short extenders, built-in LCD display and speaker for visual and audio feedback and integrated infrared temperature sensor for taking temperature measurements on the negative battery post with every test
  • Wireless capability works with Fluke Battery Analyse mobile app (Fluke BA Mobile)*
    • View profile and associated test results from the Battery Analyser
    • Send out the profile and test results via Email with (.csv) data format

* BTL20 not included with the Fluke BT-521
* Not currently compatible with Fluke Connect® app

    Specifications: Fluke 500 Series Battery Analyser

    Functions Range Resolution Accuracy BT510 BT520 BT521
    Battery Resistance / Strap Resistance1 3 mΩ 0.001 mΩ 1% + 8
    30 mΩ 0.01 mΩ 0.8% + 6
    300 mΩ 0.1 mΩ 0.8% + 6
    3000 mΩ 1 mΩ 0.8% + 6
    VDC 6 V 0.001 V 0.09% + 5
    60 V 0.01 V 0.09% + 5
    600 V 0.1 V 0.09% + 5
    1000 V 1 V 0.09% + 5
    VAC (45 Hz to 500 Hz with 800 Hz filter) 600 V 0.1 V 2% + 10
    Frequency (displayed with VAC and AAC)2 500 Hz 0.1 Hz 0.5% + 8
    AC voltage ripple (20 KHz  Max) 600 mV 0.1 mV 3% + 20
    6000 mV 1 mV 3% + 10
    ADC/AAC (with accessory Fluke i410) 400 A 1 A 3.5% + 2
    Temperature 0°C to 60°C 1°C 2°C (4°F)
    Meter mode 999 records for each measurement position with time stamp
    Sequence mode Up to 100 profiles and 100 profile templates (Each profile stores up to 450 batteries) with time stamp
    1. The measurement is based on AC injection method. The injected source signal is < 100 mA, 1 kHz.
    2. Trigger level VAC: 10 mV, AAC: 10 A
    Measurement Modes BT510 BT520 BT521
    Resistance (mΩ)
    Battery voltage
    Voltage DC
    Voltage AC and frequency  (Hz)
    Ripple volt
    Temperature of negative battery post
    DC and AC current (and frequency)
    DMM mode
    Sequence mode
    Discharge measurement mode
    Automatic measurement  save
    Wireless commumcation
    Memory view
    General Specifications
    Size (H x W x D) 22 x 10.3 x 5.8 cm (9 x 4 x 2 in)
    Weight 850 g (1.9 lb)
    Screen dimensions 7.7 x 5.6 cm (3 x 2.2 in)
    Interface USB mini
    Warranty 3 years
    Environment Specifications
    Operating temperature 0°C to 40°C
    Storage temperature -20°C to 50°C
    Lithium-ion  battery charging temperature 0°C to 40°C
    Operating humidity Non-condensing (10°C)
    ≤ 80% RH (at 10°C to 30°C)
    ≤ 75% RH (at 30°C to 40°C)
    Operating altitude Sea level to 2000 meters
    Storage altitude Sea level to 12,000 meters
    IP rating IP40
    Radio FCC Class A
    Vibration  requirements MIL-PRF-28800F: Class 2
    Drop test  requirements 1 meter
    Temperature coefficients Add 0.1 x specified accuracy for each degree C above 28°C or below 18°C
    Safety  compliance 600 V CAT III
    EMC IEC 61326
    ROHS China, Europe
    Protection class 2 Pollution Degree II
    Battery compliance UN38.3
    UL2054
    IEC62133
    2 G per IEC68-2-26, 25 G, and 29

    Fluke BT521 Advanced Battery Analyser

    Includes:

    • Battery analyser
    • 4-wire test pin (set)
    • BTL10 Basic Test Lead (set)
    • TL175 TwistGuard™ Test Leads with adapter
    • BTL21 Intelligent Test Probe Set, with extender and temperature sensor
    • i410 AC/DC Current Clamp
    • BP500 lithium-ion battery
    • BC500 AC charger
    • mini-USB cable
    • Shoulder strap
    • Belt strap
    • Magnetic hanging strap
    • FlukeView® Battery Management Software
    • Soft carrying case
    • Spare fuses (2)
    • Battery tags
    • Zero Ohm Calibration Resistor

    Fluke BT520 Battery Analyser

    Includes:

    • Battery analyser
    • 4-wire test pin (set)
    • BTL10 Basic Test Lead (set)
    • TL175 TwistGuard™ Test Leads with adapter
    • BTL20 Intelligent Test Probe Set, with extender (no temperature sensor)
    • BP500 lithium-ion battery
    • BC500 AC charger
    • mini-USB cable
    • Shoulder strap
    • Belt strap
    • Magnetic hanging strap
    • FlukeView® Battery Management Software
    • Soft carrying case
    • Spare fuses (2)
    • Battery tags
    • Zero Ohm Calibration Resistor

    Fluke BT510 Battery Analyser

    Includes:

    • Battery analyser
    • 4-wire test pin (set)
    • BTL10 Basic Test Lead (set)
    • TL175 TwistGuard™ Test Leads with adapter
    • BP500 lithium-ion battery
    • BC500 AC charger
    • mini-USB cable
    • Shoulder strap
    • Belt strap
    • Magnetic hanging strap
    • FlukeView® Battery Management Software
    • Soft carrying case
    • Spare fuses (2)
    • Zero Ohm Calibration Resistor

    Manuals

    • BT508 | Users manual
    • BT508 | Users manual supplement
    • BT510 | Users manual
    • BT510 | Users manual supplement
    • BT520 | Users manual
    • BT520 | Users manual supplement
    • BT521 | Users manual
    • BT521 | Users manual supplement
    • BT508, BT510, BT520, BT521 | Statement of memory volatility
    • BT508/BT510/BT520/BT521 | Safety sheet
    • BT508/BT510/BT520/BT521 | Safety sheet supplement
    • BT508/BT510/BT520/BT521 | Quick reference guide

    Data Sheets

    • Fluke 500 | Data Sheet

    Explore more from our collection.

    Additional information

    Models

    FLUKE-BT510, FLUKE-BT520, FLUKE-BT521 – Advanced